Technical note
Going one size up buys the wrong machine. Give us the tower rated flow and four make-up water numbers, and you get a selection report with assumptions stated.
In industrial equipment the safe habit is to go one size up. For electrochemical cooling water treatment that habit buys the wrong machine: oversized, the side-stream flow no longer matches the actual scaling load and the current density and operating strategy both have to be re-tuned; undersized, cycles of concentration cannot be raised and the investment does nothing.
Sizing depends on exactly two inputs: your circulating flow and your make-up water quality.
Our models are named after cooling tower rated flow, so a tower model number is enough — no unit conversion needed:
With two tower groups, use the combined flow (e.g. two groups totalling 330 m³/h take one JT-ECT-330). Above 2,000 m³/h, two systems are configured.
A 330 m³/h system with 80 mg/L make-up calcium hardness and one with 200 mg/L need completely different descaling duty. So we ask for four numbers:
From these we calculate the mass balance — how much calcium must be removed — then convert to current and electrode area using Faraday's law to fix the cell size and operating strategy.
The unit is an outdoor skid; no dedicated plant room is needed. On site you need:
Confirming these five items on site normally takes half a day.
Our approach is that everything can be checked item by item, so what is delivered is not a brochure:
Energy figures are given on the same basis: descaling power consumption about 3.01 kW·h/kg CaCO₃ (operating basis; 2.47 at design condition), and installed cell power about 3.0 / 4.2 / 7.5 kW for the 330 / 500 / 1000 models (excluding pumps).
Send us the cooling tower model (or circulating flow) and the make-up water analysis and we will produce a first-pass selection. Incomplete data is fine to start with — we will tell you which item is missing and how to obtain it.
Want this calculated for your plant?
Send the cooling tower rated flow and your make-up water analysis (calcium hardness / total alkalinity / chloride / TDS) and we will issue a selection report with the assumptions stated.
Request a calculation Technical FAQ
This note covers method and limits only; no unverified case data is quoted.